Fillingof-Tank
Application data sheet FAP013 GB
COUNTING OF VOLUME OF FUEL
FOR THE FILLING IN TANK TRUCKS
Customer: Louda (via Cimer)
Site: St Alban - France
Industry: Fuel distribution
Date/Qty: 2005/4 measurements
Description of the application:
The increase of the prices on the fuels involves more
controls during deliveries.
If the delivery to the customer with invoicing imposes
the use of approved and checked meters, the internal operations
with the fuel esaler are generally left with the good liking
of the operators. For example, each compartment of a tank
truck is filled while using an index like gauge.
The company named Louda wanted to go further by imposing
on its drivers a badge and a system of supervision of the
loadings carried out.
The fuels concerned are FOD, GO and Super Fuel. The flows
lie between 30 and 60 m3/h.
Description of the equipment:
The pipes which connect the tanks of storage and the
loading arms are in 3 inches (89 mm).
They were equipped with clamp-on probes ref. SE-1515
assembled in mode W and with supports ref. SU-1517.
MINISONIC 600-B, therefore the dual-pipe version was
selected for price reasons. As there are 4 pipes, there
are 2 converters. This system has, in term of budget, nothing
comparable with 4 approved counting benches. Here, only
supervision is concerned. However, thanks to the shortest
response time and the excellent repeatability of the MINISONIC,
each date and time operation of loading are recorded and
allow to the Louda company to supervise the activity in
real time. Four sites located in the South West of France
are to be equipped.
Complementary services:
A complementary and essential supply is the supervision
system with badge reader and taking into account our information
of counting. This service was entrusted by Louda to a regional
company.
Another service, for which we assisted Cimer and Louda,
is the adjustment of the equipment to satisfy the accuracy.
For this, a reference tank and a tank truck to carry out
the transfers had been placed at our disposal.
Particular technical specifications:
The awaited accuracy is about 1 to 2%, but with a repeatability
of 0.5%.
We foresee in a seasonal way a checking with possible
adjustment, the products concerned having characteristics
to be sensitive to the temperature(viscosity).
The absence of information from the flowmeter to the
supervision system (contact of increment of volume) stops
automatically the transfer pump.
|